To convert kVA to kW, multiply the kVA by the power factor. Most generators are rated at a power factor of 0.8, so a 10 kVA generator gives 8 kW and a 100 kVA generator gives 80 kW of real power. The calculator above lets you set any power factor, and the table below covers the usual values.
kVA, kW and power factor
kVA measures apparent power: volts times amps. kW measures real power: the part that actually runs motors, lights and heaters. The ratio between them is the power factor, a number between 0 and 1.
- kW = kVA × power factor
- kVA = kW ÷ power factor
Heaters, kettles and incandescent lamps have a power factor of 1, so their kVA and kW are the same. Motors, compressors and older fluorescent fittings have lower power factors. Modern electronics with power factor correction usually run at 0.95 or above.
kVA to kW table
| kVA | PF 0.8 | PF 0.85 | PF 0.9 | PF 1 |
|---|---|---|---|---|
| 1 kVA | 0.8 kW | 0.85 kW | 0.9 kW | 1 kW |
| 2 kVA | 1.6 kW | 1.7 kW | 1.8 kW | 2 kW |
| 3 kVA | 2.4 kW | 2.55 kW | 2.7 kW | 3 kW |
| 5 kVA | 4 kW | 4.25 kW | 4.5 kW | 5 kW |
| 7.5 kVA | 6 kW | 6.38 kW | 6.75 kW | 7.5 kW |
| 10 kVA | 8 kW | 8.5 kW | 9 kW | 10 kW |
| 15 kVA | 12 kW | 12.75 kW | 13.5 kW | 15 kW |
| 20 kVA | 16 kW | 17 kW | 18 kW | 20 kW |
| 25 kVA | 20 kW | 21.25 kW | 22.5 kW | 25 kW |
| 30 kVA | 24 kW | 25.5 kW | 27 kW | 30 kW |
| 40 kVA | 32 kW | 34 kW | 36 kW | 40 kW |
| 50 kVA | 40 kW | 42.5 kW | 45 kW | 50 kW |
| 62.5 kVA | 50 kW | 53.13 kW | 56.25 kW | 62.5 kW |
| 75 kVA | 60 kW | 63.75 kW | 67.5 kW | 75 kW |
| 100 kVA | 80 kW | 85 kW | 90 kW | 100 kW |
| 125 kVA | 100 kW | 106.3 kW | 112.5 kW | 125 kW |
| 150 kVA | 120 kW | 127.5 kW | 135 kW | 150 kW |
| 200 kVA | 160 kW | 170 kW | 180 kW | 200 kW |
| 250 kVA | 200 kW | 212.5 kW | 225 kW | 250 kW |
| 500 kVA | 400 kW | 425 kW | 450 kW | 500 kW |
| 1,000 kVA | 800 kW | 850 kW | 900 kW | 1,000 kW |
Why generators and UPS units are rated in kVA
The alternator in a generator and the transformer in a UPS heat up according to the current they carry, not the real power the load uses. So manufacturers state how many kVA the unit can supply, and usually add the kW figure at a standard power factor. For diesel and petrol generators that standard is 0.8. Many modern UPS units are rated at 0.9 or 1.0, so check the datasheet.
When you size a generator, add up the kW of everything you want to run, divide by 0.8 to get the kVA, and leave headroom for motor starting currents. To turn the rating into current for cables and breakers, use the kVA to amps calculator.
Worked examples
- 5 kVA generator at 0.8: 5 × 0.8 = 4 kW.
- 62.5 kVA generator at 0.8: 62.5 × 0.8 = 50 kW, a common standby size.
- 3 kVA UPS at 0.9: 3 × 0.9 = 2.7 kW.
- Going the other way: a 40 kW load at 0.8 needs 40 ÷ 0.8 = 50 kVA.
Frequently asked questions
How many kW is 1 kVA?
1 kVA is 0.8 kW at a power factor of 0.8, 0.9 kW at 0.9 and 1 kW at a power factor of 1.
Is kVA the same as kW?
Only when the power factor is 1. For most real loads kVA is a little higher than kW.
What power factor should I use?
Use 0.8 for generators unless the datasheet says otherwise, the stated power factor for a UPS, and the nameplate value for motors. If you have nothing else, 0.8 is a safe, conservative choice.
How do I convert kW to kVA?
Divide by the power factor. 16 kW at 0.8 is 20 kVA. In the calculator above, type the kW in the right hand box and it works it out.